System-main Approx Age of System: 2 years ago Refrigerant Type- R410a Metering Device-TXV SP/HP:118/321 SLT/LLT:54/94 VSAT/LSAT- 40/101 Superheat/Subcool- 14/7.1 Outdoor Entering Air Temp-90 Outdoor Fan FLA-1.0 Compressor RLA/LRA-NA Contactor Voltage-241/27 Capacitor Rating- NA Indoor Return Dry Bulb Temp-74 Return Wet Bulb Temp-64 Supply Temp- 49 Temperature Difference-25 Required Difference-16-24 Blower FLA- 7.0 Filter Sizes – 20x25x4 Changed Filters – Y customer supplied Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes-no issues found at this time. Unit is cooling and operating within manufactured specs. Scheduled next tune up date: 1/29 8-10