System- downstairs Approx Age of System: 2 Refrigerant Type- R410a Metering Device- TXV SP/HP: 136/350 SLT/LLT: 62/99 VSAT/LSAT- 47/105 Superheat/Subcool- 16/7 Outdoor Entering Air Temp- 87 Outdoor Fan FLA- 0.9 Compressor RLA/LRA- 8.8/88.8 (83.0) Contactor Voltage- 249 Capacitor Rating- 45/5 Indoor Return Dry Bulb Temp- 74 Return Wet Bulb Temp- 63 Supply Temp- 56 Temperature Difference- 18 Required Difference- 15x20 Blower FLA- 6.1 Filter Sizes – 16x25x4 Changed Filters – N ( Customer will change) Blew out drain line: N Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Performed ac tuneup. System was operational upon arrival. Compressor is over amping on startup- this is indicated by the LRA rating. System- upstairs Approx Age of System: 2 Refrigerant Type- R410a Metering Device- TXV SP/HP: 137/319 SLT/LLT: 71/100 VSAT/LSAT- 49/101 Superheat/Subcool- 22/1 Outdoor Entering Air Temp- 87 Outdoor Fan FLA-