30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for the woodlands, tx


Map of The Woodlands TX
Jeremy D.

Jeremy D.


Job Checkin

AC Diagnostic System: Upstairs Refrigerant Type R410A Metering Device- TXV SP/HP 142/379 SLT/LLT 63/98 VSAT/LSAT 50/112 SH/SC 13/14 Outdoor Entering Air Temperature 91 Filter Size(s) 20x25x1 Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes: On arrival blower motor and compressor were operational. Condenser fan motor was not operational. Checked condenser electrical. No issue. Checked fan motor shaft and bearings. Shaft is seized. Informed Mr. Sangwan. Due to age and cost of repair I recommended replacement options. Mr. Sangwan chose to repair. Replaced fan and capacitor. Checked operation. Checked operating temperatures and pressures. Water is present in emergency drain pan. Mr. Sangwan chose to take no action at this time.