System- 1 system Approx Age of System: 4 year old Refrigerant Type- R410a Metering Device- TXV SP/HP:113/231 SLT/LLT:62/76 VSAT/LSAT-40/82 Superheat/Subcool-22/6.7 Outdoor Entering Air Temp-80 Outdoor Fan FLA- O.98 Compressor RLA/LRA-13.23/133.5 Contactor Voltage-245 Capacitor Rating-70/5 Indoor Return Dry Bulb Temp-68 Return Wet Bulb Temp-61 Supply Temp- 48 Temperature Difference-20 Required Difference-16-20 Blower FLA- 3.6 Filter Sizes –20x25x4 Changed Filters – No clean Blew out drain line: Yes Notes- *No way to blowout drain lines or inline safety switch would recommend installing *would recommend air purification, to help kill and prevent organic growth also kills bacteria in the home. *customer had me install blow out valve and clear drain lines Scheduled next tune up date: 11/4/20 10-2