System- Approx Age of System: 3yrs Refrigerant Type- R410a Metering Device-TXV SP/HP: 114/292 SLT/LLT: 47/86 VSAT/LSAT- 37/93 Superheat/Subcool- 9/6 Outdoor Entering Air Temp-75 Outdoor Fan FLA-1.2 Compressor RLA/LRA- 9.2/*** Contactor Voltage- 240/26 Capacitor Rating-*** Indoor Return Dry Bulb Temp- 67 Return Wet Bulb Temp- 58 Supply Temp- 50 Temperature Difference- 17 Required Difference- 16-20 Blower FLA-4.9 Filter Sizes – 12x24x1 20x30x1 1 Changed Filters – Acceptable Blew out drain line: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. All other components showed no visible issues at this time. Scheduled next tune up date: 11-02-20 8-10am