System- Single Approx Age of System: 14 Refrigerant Type- R22 Metering Device- TXV SP/HP: 68/196 SLT/LLT: 52/96 VSAT/LSAT- 39/99 Superheat/Subcool- 13/3 Outdoor Entering Air Temp- 86 Outdoor Fan FLA- 1.2 Compressor RLA/LRA- 9.2/89.1 Contactor Voltage- 242 Capacitor Rating-60/10 Indoor Return Dry Bulb Temp-72 Return Wet Bulb Temp- 55 Supply Temp- 49 Temperature Difference- 23 Required Difference-21 Blower FLA- 6.8 Filter Sizes – 20x30x1 Changed Filters – N (clean) Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- performed ac tuneup. System was operational upon arrival. System operating good at this time. Hardstart kit installed, run capacitor is a new turbo200X. Blowout valve and emergency pan switch installed. Recommended installation of an in-line float switch.