30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for tomball, tx


Map of Tomball TX
Juan  M.

Juan M.


Job Checkin

System- upstairs Approx Age of System: 15 Refrigerant Type- R22 / Metering Device- Fixed Orifice / SP/HP: 61/175 SLT/LLT: 61/89 VSAT/LSAT- 35/92 Superheat/Subcool- 25/2 Outdoor Entering Air Temp- Outdoor Fan FLA- .7 Compressor RLA/LRA- 6.7 Contactor Voltage- 244 Capacitor Rating- Turbo Indoor Return Dry Bulb Temp - 74 Return Wet Bulb Temp- 66 Supply Temp- 55 Temperature Difference- 19 Required Difference- 15-20 Blower FLA- 3.7 Filter Sizes – 20x25x1 Changed Filters – N customer will Blew out drain line: N no blow out Returned tstat to original settings: Y Unit operational; prior to leaving: Y with issues Notes- Scheduled next tune up date: System- downstairs Approx Age of System: 1 Refrigerant Type- R410a Metering Device- TXV SP/HP:116/303 SLT/LLT: 54/77 VSAT/LSAT- 40/96 Superheat/Subcool- 15/18 Outdoor Entering Air Temp- Outdoor Fan FLA- .3 Compressor RLA/LRA-5.7/62 Contactor Voltage-243 Capacitor Rating- 40/5 Actual 40/5 Indoor