System- Single Approx Age of System: 1 Refrigerant Type- R410a Metering Device- TXV SP/HP: 109/307 SLT/LLT: 48/83 VSAT/LSAT- 36/97 Superheat/Subcool- 12/13 Outdoor Entering Air Temp- 81 Outdoor Fan FLA- 0.9 Compressor RLA/LRA- 8.4/76.1 Contactor Voltage- 244 Capacitor Rating- 40/5 Indoor Return Dry Bulb Temp- 71 Return Wet Bulb Temp- 58 Supply Temp- 50 Temperature Difference-20 Required Difference- 20 Blower FLA- 4.1 Filter Sizes – 12x12 (2), 12x20 Changed Filters – N Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- performed ac tuneup. System was operational upon arrival. Angel expressed interest in the air scrubber but does not want to do it on this visit. Scheduled next tune up date: 01/14