30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for willis, tx


Map of Willis TX
Jeremy D.

Jeremy D.


Job Checkin

System- Main Approx Age of System: 5yrs Refrigerant Type- R410a Metering Device- Fixed Orifice SP/HP: 122/303 SLT/LLT: 59/86 VSAT/LSAT- 41/96 Superheat/Subcool- 17/10 Outdoor Entering Air Temp- 82 Outdoor Fan FLA- 1.2 Compressor RLA/LRA- 10.3/117 Contactor Voltage-242/26 Capacitor Rating- 68.01/14.75 Indoor Return Dry Bulb Temp-75 Return Wet Bulb Temp- 59 Supply Temp- 55 Temperature Difference- 20 Required Difference- 16-20 Filter Sizes – 20x30x1 Changed Filters – Acceptable Blew out drain line: Y Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Condenser LRA is over rating of 117a. All other components showed no visible issues at this time. Recommend compressor saver-(to reduce amp and extend equipment life). Installed compressor saver. Checked operation. Scheduled next tune up date