Diagnostic Found 55/5uf run cap failed. Replaced with Turbo 200. System function restored. 90/292 psi 58/112 lt 52/130 sat 4/16 shsc Condenser coil is starting to deteriorate. System is running very hot. Compressor is struggling audibly at start up. System utilizes r22. Based on age, conditions and operational concerns - system replacement is recommended. Trust owned home.