Commercial service call in Dallas Upon arrival found food room not cooling. Checked condenser on roof top and found contactor pulled in but unit not running. Found that the system had a bad 70/5 dual run cap. Replaced cap and system came on. Checked amp draws and pressures, checked supply air 57 and return air at 77. System is now cooling properly at this time.