AC Repair to avoid new HVAC installation - Front unit was leaking water. Checked drain line. Found condensate trap clogged and overflowing into the return duct. Cleared out trap on drain. Flushed out pan. Checked for proper drainage. Ran unit through both stages of cooling. Checked charge on system. Checked electrical components. Found a dual 10/10 mff run capacitor on condensing fan motors is weal/below parameters. Recommend replacing capacitor. Condensing coil is dirty and needs to be cleaned. Dirty condensing cooling is causing high refrigerant pressures and temperatures. Checked for water access. Found a mop sink in men's bathroom. We can run hose out back door then up to the roof. Will need about 400' of hose. Checked blower amps and belt. Unit is cooling but as outdoor temp gets higher unit will struggle to cool properly. Bad/weak capacitor will make motors over amp and go out on internal temp causing unit not to cool or ruin motors.