Springtime HVAC Maintenance for a residential customer near Buddy Graham Park. Came out today on 1 system maintenance Changed 3x 10x20x1 from home depot Checked amp draws checked temp split checked contactors checked run capacitors checked bearings checked blades checked electrical connections checked pressures washed outdoor coil Found Dirty condenser / cleaned during visit. Bad 5mfd run cap / replaced during visit. 1.3 rated amps on condenser fan motor / actual Amp draws 5.4 possible part failure / replaced condenser fan motor during visit.