Came out on one system maintenance. Checked Amp draws checked temperature split over unit checked electrical connections checked contactor checked run capacitors checked bearings checked blades checked drain lines checked coils checked air scrubber uv light Found Dual run cap suppose to be 40/10 we are reading 39.5/7.4 which is bad needs to be replaced No surge protection on any equipment. Dusty duct work causing motor to work harder.