521 J PL 625
Plano , TX 75074
469-252-0599

Job Locations
for murphy, tx


Map of Murphy TX
Darius M.

Darius M.


Job Checkin

Found water in both secondary drain pans. Drain appears to have a clogged. Upstairs system is installed improperly causing low airflow through evaporator coil and system is low on refrigerant (410a). Refrigerant leaks may be attributed to installation of equipment. Recommend replacing evaporator. Unit doesn't have any available warranty on system. Condensing unit is a 5 ton but furnace only has a 4 ton blower capacity. Unit is mismatched. Condensing coil is very dirty and dual capacitor is bad. System has never been at full capacity due to installation. Downstairs system lis low on r22, condensing coil is dirty, and evaporator coil appears to have leaks. Recommend replacing equipment due to age and condition. System may also have metering issues as well. Duct systems are undersized. Wasn't able to get approval for anything owner is at work. Daughter will relay information to him.