Upon arrival found the front office unit was not cooling and the thermostat was off. Checked RTU and found no power present. Found breaker tripped. Reset breaker and checked rTU and found that the first stage compressor was locked up and causing high amp draws to trip breaker. Disconnected 1st stage compressor to use 2nd stage compressor to cooling down area until compressor is replaced. System is only running at 50% capacity. Waiting on morsco to give me a price for compressor so I can send estimate over to replace compressor.