Thomas W.

Thomas W.


Job Checkin

Customer called due to no cold air not cooling. Upon arrival the unit was off. I turned the unit on at the thermostat and went downstairs to the system and watched it run. Went outside to the condenser and watched it run. Turned the unit off at the switch. Removed the panel to the evaporator coil. Inspected the coils for any dust build up. Coils are clean. Removed the panels to the furnace. Checked the electrical connections to make sure they were properly secure. Checked the blower motor and fan for any dust build up. Filter was recently changed and clean. Took an amp draw for the blower motor, running within the manufacture’s specs. Checked the condensate pump. Poured water until it pumped out properly. Went outside to the condenser. Took an amp draw for the fan, .83. Took an amp draw for the compressor, 7.04. Contactor and capacitor are both running within the manufacture’s specs. Checked the coils for any dirt build up. Coils are clean. Hooked my gauges up and found the pressures t