Model # NCPE-424-1010 Serial # 259C9224 Completed a preventative maintenance on a 3 year old air conditioner. Customer changed 25x14x1 filter the temperature split was 20 degrees. Made sure unit was draining properly. Then I performed a amperage readings on compressor 11.2 amps and condenser fan motor 1.0 amps, after that I checked the capacitor and contactor both are operating properly. I tested the capacitor on the indoor blower motor and it is not running in the proper range, me and the customer decided it would be best to replace it now he also paid for a cud club membership. System is operating properly at this point.