Came out today for a condenser not running. Upon inspection I ohm out the capacitor and got a reading of 15 +1. The capacitor was also extremely swollen. I replaced the capacitor with a 40+5. The system is operating properly at this time. I explained to the customer that this is something we check during preventative maintenance and that's something he should be getting done yearly.