Control fuse in furnace blown. Traced short to defrost board in outdoor unit. 10 ohms across R and C. I wired heat pump for cooling only for temporary service. Installed Honeywell focus pro heat pump thermostat. Installed wet switch in safety pan. Wired in the freeze stat and condensate pump float safety. Returning 1F80-0471 to office.