Clean and check electric furnace and heat pump. Tested heating elements. Tested sequencers. Checked voltage & amp draw of blower. Furnace amp draw: 62.2. Voltage: 236. Test capacitors. Found dual run capacitor weak: 36%low. Replaced capacitor Under parts only warranty and tested amp draw. Compressor:10.5A .Condenser fan: 0.9A.ambient: 45 .liquid line: 94 . Return air: 65 .supply air: 91. Clean and check humidifier, replace pad, checked water flow and drain. Found humidistat contacts not closing. Replaced humidistat. Clean and check electric furnace in crawlspace for rear addition. Tested heating elements. Tested sequencers. Checked voltage & amp draw of blower. Test capacitor.