Service was excellent. On-time, quietly competent and quickly done.
Did a great job diagnosing the problem and performing the necessary fix.
We won't have the A/C repaired totally until Roger can secure a part from Carrier, so far we are very pleased with the fine service we are receiving from CLASSIC AIR CARE! We appreciate the temporary fix that Roger performed!
Moving Day. Frigid temperatures. No heat. We were in a jam and Classic Aire Care saved the day! We are so thankful for the professional and speedy attention to our furnace mishap. With Sean's help, we were able to get back on (a much warmer) track to move into our new home. Thank you!
they don't hesitate to come back free of charge after a service call if something isn't right.
As it turned out we had an area of common interest (hobby) which added some friendly conversation while not interfering with the repair.
I am happy with Classic Aire Care's service. They were able to provide same day service, all the employees were friendly and customer oriented and the price was reasonable. I will definitely continue to use them in the future.
Found furnace locked out: 2flashes. Found flame current very weak. Cleaned flame sensor and tested: 2.2uA. Found blower dropped out apoun engaging stage 2 heat!! Corrected wiring of blower. Inducer: 0.32/1.04A. Blower: 3.9/5.1A. Checked temperature rise: 30/48. Checked draft: 0.04”. Does not appear to have proper flue liner in masonry chimney. Suggestions: Furnace is about 22 years old. replace furnace soon. Recommend installing new flue liner to protect chimney.
Cleaned & checked condensing gas furnace. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked drain. Checked voltage & amp draw of motors. Blower: 1.3A/4.9A . Inducer: 0.2/0.62A . Gas pressure: -/1.7/3.5 inches water column. Temperature rise: H:70 . Clean and check humidifier, replace pad, checked water flow and drain. The humidifier pads that we delivered are the wrong size . I am returning three #12 humidifier pads to the office . need to refund customer $49.
I removed blower door to find flashing code 4: open primary limit. There was no voltage to limit and inducer would periodically turn on. I replaced furnace control board, including new igniter. Tested operation. Inducer: .37 A. Blower: 4.0 A.
Cleaned & checked gas furnace. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked voltage & amp draw of motors. Test capacitor. Replaced air filter. Clean and check humidifier, replace pad, checked water flow and drain. Blower: 4.8A. Inducer: 1.18A. Gas pressure: 3.5 inches water column. Temperature rise: 54 . Supply: 128. Return: 74 . Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Compressor: 8.2A . Condenser fan: 0.7A. Blower: 5.4A . ambient: 56 . liquid line: 62. suction line: 44 . metering device: TXV . Return air: 71 . supply air: 50.
I removed motor module from murder. I’m doubt motor windings: OK. Installed new module and adapter ring and harness. Tested operation and found Motor would not run. Blower wheel rocks back and forth. I tested wiring harness continuity. I put old motor module back on for temporary cooling. Need to return with another replacement module. Work suggested: need to call Carrier and double check part numbers. Need to order New motor module. Call customer ASAP when availability is known.
No cooling by passed blower module till part is replaced
Serviced air conditioner and replaced filter
AC maintenance! Replace run capacitor for blower and dual capacitor for condenser