Cleaned & checked gas furnace. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked voltage & amp draw of motors. Test capacitor. Replaced air filter. Clean and check humidifier, replace pad, checked water flow and drain. Blower: 4.8A. Inducer: 1.18A. Gas pressure: 3.5 inches water column. Temperature rise: 54 . Supply: 128. Return: 74 . Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Compressor: 8.2A . Condenser fan: 0.7A. Blower: 5.4A . ambient: 56 . liquid line: 62. suction line: 44 . metering device: TXV . Return air: 71 . supply air: 50.