John M.

John M.


Job Checkin

Work Done: Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Replaced air filter. Compressor: 7.8A.Condenser fan: .72A . Blower: 5.6A.ambient: 64 .liquid line: 65 .suction line: 50 .metering device: Piston . Suction pressure:60(34). SH: 16. T:10 . Return air: 66 .supply air: 45.5 .wet bulb: 53 .