Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Checked filter. Compressor:9.0A . Condenser fan: 0.92A . Blower: 6.9A . ambient: 77 . liquid line: 82 . suction line: 40 . metering device: piston . Suction pressure: 118(40) . Return air: 69 . supply air: 49 .