1276 N. Warson
St. Louis, MO 63132
(314) 352-1111

Job Locations
for eureka, mo


Map of Eureka MO
John M.

John M.


Job Checkin

Pumped down system. Removed and replaced evaporator coil. Pressurize and leak check connections. Evacuate low side and topped off Freon level. Compressor:9.3A . Condenser fan: 0.84A. ambient: 83. liquid line: 90 . suction line: 54 metering device: TXV . Suction pressure:119(40) . head pressure: 318(99). Return air: 69.