John M.

John M.


Job Checkin

Found burnt wire connection at dual run capacitor. Capacitor weak and seal melted. Replaced capacitor and tested cooling operation. Compressor: 13A . Condenser fan: 1.26A . ambient: 83 . liquid line: 83 . suction line: 53 . metering device: TXV . Suction pressure: 70(41) . head pressure: 190(102) .