1276 N. Warson
St. Louis, MO 63132
(314) 352-1111

Local Reviews
for florissant, mo

Rated 4.9 out of 5 stars based on 129 customer reviews

John was excellent. He took the time to explain a few strategies I needed to be reminded about.

I delayed in filling this out to be sure our AC kept working. John was very professional the entire time in explaining what to him must be very basic facts in keeping our AC bills in daily usage down. I appreciated his quality of service.

  • Overall Experience
  • Quality
  • Price
  • Convenience

good service

I don't have one

  • Overall Experience
  • Quality
  • Price
  • Convenience

Super service

John arrived promptly, checked everything insid and out. My air conditioner got a clean bill of health. Love these guys at Classic Aire.

  • Overall Experience
  • Quality
  • Price
  • Convenience

EXCELLENT SERVICE!!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service affordable price

  • Overall Experience
  • Quality
  • Price
  • Convenience

Professional

John was on time (early actually), very friendly, and professional during this job. I appreciate his time and knowledge.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service/Advice

  • Overall Experience
  • Quality
  • Price
  • Convenience

pls provide copies for my records

I need a copy of the work results from today at 3633 Marietta for my records - I can't really rate the service since it was done at a rental property until I speak to my renter

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

They came out to do springtime maintenance on the air conditioning unit they installed in November and found a problem that they came back and fixed, at no cost to me!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Both technicians were very prompt and efficient. Explained things well and offered suggestions.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Professional and knowledgeable

The installation of the humidifiers was a time consuming effort and these two gentlemen kept a steady pace. When finished the operation of the humidifiers was explained in detail. The area was left clean. And that is why we have we are with Classic Aire

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent services

Roger was very helpful in explaining what the issue was and a professional, very low cost

  • Overall Experience
  • Quality
  • Price
  • Convenience

great efficent friendly

HELPFUL INFORMATION EXP[AINED OPTIONS

  • Overall Experience
  • Quality
  • Price
  • Convenience

Nice, very great job!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for florissant, mo

John M.

John M. Job Checkin

Cleaned & checked gas furnace. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked voltage & amp draw of motors. Test capacitor. Replaced air filter. Blower: 5.7A . Inducer: 1.2A Temperature rise: 48 . Supply: 119. Return: 71 .


John M.

John M. Job Checkin

I found humidifier drain tubing clogged! I cleared the blockage. Found humidifier solenoid valve stuck open! Also due for water panel replacement. I replaced furnace air filter. Tested operation. Suggestions: Replace humidifier with larger model: $716. PMA Discount applies.


John M.

John M. Job Checkin

Cleaned & checked 2 gas furnaces. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked voltage & amp draw of motors. Test capacitors. First floor system: flame sensor current dropping below minimum. Clean flame sensor and tested: 2.7 micro amps. Replaced air filter. Blower: 6.6A . Inducer: 1.38A . Gas pressure: 3.4 inches water column. Temperature rise: 47 . Supply: 114. Return: 67 . Second floor system: Replaced air filter. Blower: 5.8A . Inducer: 1.45A. Gas pressure:3.4 inches water column. Temperature rise: 46 . Supply: 115. Return: 69 .


Jeff K.

Jeff K. Job Checkin

Furnace maintenance today! Signed up for new maintenance plan


Jeff K.

Jeff K. Job Checkin

AC maintenance! System looks good


Roger H.

Roger H. Job Checkin

Serviced ac and furnace


Roger H.

Roger H. Job Checkin

Ac check up


John M.

John M. Job Checkin

I found condenser fan motor bearings going bad. Found condenser fan motor capacitor very weak. Motor drawing 20% over full load amps. Also compressor capacitor very weak. Compressor drawing high amps. Freon level only slightly low: within 10 degrees of charging chart. Replaced fan capacitor for temporary cooling and tested amp draw: 0.86A.


John M.

John M. Job Checkin

Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Cleaned condenser coil. Checked filter: dirty MERV 16. More than 1” drop. I installed temporary 1 inch filter. Need to order MERV 16 air cleaner media. Checked Freon level: Low again. I talked of Freon level enough to get system cooling nearly full capacity. System is still approximately 20% low on Freon. Superheat: 16. Sub :: zero.


John M.

John M. Job Checkin

Cleaned and checked air conditioner. Checked and cleaned out drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Checked filter. Compressor: 14.9A. Condenser fan: 1A . Blower: 4.7A, 1400. ambient: 90 . liquid line: 92 . suction line: 49. metering device: TXV . Return air: 71 . supply air: 51.5 . wet bulb: 56.


John M.

John M. Job Checkin

Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Found run dual capacitor weak: 11%low, Compressor side. Replaced capacitor and tested amp draw. Checked Freon level. Cleaned condenser coil. Replaced air filter. Compressor: 9.7A. Condenser fan: 0.83A . Blower: 6.0A . ambient: 85 . liquid line: 90. suction line: 48 . metering device: piston . Suction pressure: 76(45). Return air: 79 . supply air: 57.5. wet bulb: 64.


John M.

John M. Job Checkin

Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Compressor: 9.3A. Condenser fan: 0.8A . Blower: 3.0A . ambient: 84 . liquid line: 89, dirty . suction line: 41. CC: dry. metering device: piston. Return air: 79. supply air: 57 . wet bulb: 68.5. Temperature drop: 22. Target: 15.5. Airflow is very poor mainly due to very restrictive supply duct transition into attic. Also blower wheel is dirty due to running without a filter, further reducing airflow. Approximately 65 feet of copper line set. Cleaned & checked gas furnace. Inspected heat exchanger & flue venting. cleaned burners & flame sensor. Checked voltage & amp draw of motors. Test capacitor. Gas piping to furnace and water heater does not have drip legs (per gas code). Also water heater vent diverter not attached to water heater. Furnace room has no combustion air venting. Workshop suggested: remov


Roger H.

Roger H. Job Checkin

Replaced bad condenser fan motor


John M.

John M. Job Checkin

Found discharge line center bad. Stuck open. I wired around sensor for temporary cooling. Need to order new discharge line sensor. I also found air conditioner in need of cleaning. Customer purchased maintenance plan today. Work suggested: need to order warranty part and schedule replacement. Has cooling. Recommend scheduling first maintenance visit also.


Roger H.

Roger H. Job Checkin

Found leaking evaporater coil,getting estimate on replacing