Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Found run dual capacitor weak: 11%low, Compressor side. Replaced capacitor and tested amp draw. Checked Freon level. Cleaned condenser coil. Replaced air filter. Compressor: 9.7A. Condenser fan: 0.83A . Blower: 6.0A . ambient: 85 . liquid line: 90. suction line: 48 . metering device: piston . Suction pressure: 76(45). Return air: 79 . supply air: 57.5. wet bulb: 64.