1276 N. Warson
St. Louis, MO 63132
(314) 352-1111

Job Locations
for frontenac, mo


Map of Frontenac MO
John M.

John M.


Job Checkin

Cleaned and checked 2 air conditioners. Checked drains. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon levels. Cleaned condenser coils. North system (kitchen): Replaced air cleaner media. Added 2# of 410A Freon. Compressor: /12.8A . Condenser fan: 0.9A. Blower: 1.8/6.7A . ambient: 76. liquid line: 99, dirty . suction line: 49 . metering device: TXV. wet bulb: 58. South system (bedrooms): Replaced clogged air filter. I found blower not staging properly! I installed an isolation relay for proper blower speeds for cooling stage 1 and 2. Compressor: 4.4/8.3A. Condenser fan: 0.65A. Blower: 1.3/4.0A . ambient: 77 . liquid line: 74 . suction line: 44 . metering device: TXV . Return air: 67. supply air: 49/ . wet bulb: 58. Work suggested: North system: Replace air cleaner media every 6 months. Freon leak search: $189. Freon leak repair: $? South system: replace air filter every month or two.