Found condenser fan motor bad. Bad bearings. Replaced condenser fan motor. 1/4 Horse power, 1075. Installed 7.5 µF capacitor. Checked Freon level. Checked voltage & amp draw of motors. Suction: 63 (36) suction line: 68. Wet bulb: 66. Return air: 79.5. Supply air: 59.5. Superheat: 32. Target 23. Sub cooling: 24! Fan: 1.6A. Condenser coil is dirty. Has dirty inner row coil. Recommend splitting coil to wash.