AC was cooling when I arrived. Customer flushed out drain tubing. Has 3’ trap. Compressor: 8.2A .Condenser fan: 0.67A.ambient: 82.liquid line: 112 .suction line: 58 .metering device: TXV . Suction pressure: 137(48).head pressure: 455(126) . Return air: 75.5 .supply air: 56 .wet bulb: 64 . Condenser coil is packed with dirt. Needs thorough flushing of coil. Customer declined at this time.