Job Checkin

Work Done: Cleaned and checked 2 air conditioners. Checked drains. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon levels. Cleaned condenser coils. Second floor system: installed PURE-AIR maintenance kit for air purification system. Compressor: 9.5A .Condenser fan: .78A . Blower: 1600 .ambient: 68 .liquid line: 68.suction line: 57 .metering device: TXV . Suction pressure: 101(32). First floor system: Found blower run capacitor too weak. Replaced capacitor and tested amp draw of 3/4hp blower. Compressor: 12.3A .Condenser fan: 1.4A Blower: 9.1A.ambient: 76. metering device: TXV . Suction pressure: 55-62. Return air: 67.supply air:49-52 .wet bulb: 59 . SC: 3-10. SH: 16-22. (Noncond)