1276 N. Warson
St. Louis, MO 63132
(314) 352-1111

Job Locations
for webster groves, mo


Map of Webster Groves MO
John M.

John M.


Job Checkin

Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Found wire connection overheating at capacitor. Found superheat off target. Also, Schrader caps missing. Back-flushed condenser coil with Water-Saber. I topped off Freon(410A) level and installed new brass caps. Compressor:11.6A . Condenser fan: 0.68A . Blower: 5.8A . ambient: 81 . suction line: 38. metering device: piston . Suction pressure: 114(38). Return air: 67.5 . supply air: 50.5. wet bulb:59 . Work suggested: remove box setting on the drain line. Freon leak search: $189. Freon leak repair: $?