Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Replaced air filter. Compressor: 8.9a/12.4A . Condenser fan: 0.96A . Blower: add 10%. 1540. ambient: 87 . liquid line: 93 . suction line: 49. metering device: TXV . Suction pressure: 119(41) . Return air: 71 . supply air: was43.5/45.5 . wet bulb: 58 . Found dual run capacitor weak: 12%low, fan side. Replaced capacitor under parts and labor warranty and tested amp draw.