Cleaned and checked 2 air conditioners. Checked drains. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon levels. Cleaned condenser coils. Checked filters. Main floor system: Found blower run capacitor weak: 42%low! Replaced capacitor and tested amp draw. Compressor: 10A . Condenser fan: 1.2A . Blower:was9.4A . ambient: 76 . liquid line: 80, dirty . suction line: 52 . metering device: TXV . Suction pressure:113(36) . Return air: 70 . supply air: 49.5 . wet bulb: 58 . Basement system: Compressor: 5.45A . Condenser fan: 0.79A . Blower: 4.0A . ambient: 76 . liquid line: 79 . suction line: 56 . metering device: TXV . Return air: 69.5. supply air: 51 . wet bulb: 58 .