Work Done: Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Found dual run capacitor weak: 31%low. Replaced capacitor and tested amp draw. Checked Freon level. Cleaned condenser coil. Found washable filter restricting airflow. Removed filter for testing. Dryer vent is right next to air-conditioner. I flushed out dirt and plant from condenser coil. Compressor: 20.9A, was 23.3A. Condenser fan:1.5A . Blower: 10.5A, w/o filter. .ambient: 55 .liquid line: was67 .suction line: 46 .metering device:piston . Suction pressure: 57. Return air:65 Work Suggested: recommend fiberglass type air filters. Recommend moving clothes dryer vent.