Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Checked Freon level. Cleaned condenser coil. Checked filter. Adjust blower. Compressor: 6.7A . Condenser fan: 0.65A . Blower: 3.0A . ambient:89 . liquid line: 94, dirty . suction line: 51 . metering device: piston . Suction pressure: 130(45) . Return air: 71 . supply air: 53 . wet bulb: 59.5 ,RH: 56%.