No ac. Found 45/5 capacitor on condenser has failed. Both sides at zero. Replaced with new capacitor which tests at 45.6/5.07. Compressor amp draw 6.46a, fan amp draw.54 amp. 237vac. 23° temperature split. Washed condenser coil.