No cool loganville. Completed diagnostic. Found system very low on refrigerant. Leaking out of evap coil. System only 7 years old. Everything else clean and working in range of manufacturing spec. Ordered new coil will return next week to replace. Filled system with 410a refrigerant to get them by until I return.