System was frozen up upon arrival, suction line was freezing throughout the basement as well as towards the compressor. Upon further inspection i found the indoor coil to be thawed out, leak searched coil and found leak on capillary tube on the far bottom left of coil. Oil spillage has caused a lot of corrosion on this point. Megged out compressor and compressor is starting to go, within the good parameters (700 range) but still under 1000. No warranty on coil. Jeff will be out today between 5-7 to give both estimates. Outdoor coil is 100% clogged in some areas.