RTU #5 NOT WORKING. FOUND UNIT TO BE CYCLING ON HOGH HEAD PRESSURE. COMPRESSOR IS DRAWING VERY HIGH AMPS AND IS SCALDING HOT WITHIN A MINITE OF RUNNING. OHMED OUT COMP. AND BEWTWEEN EACH WINDING WAS OKAY. .7 BETWEEN EACH TERMINAL. WHEN GOING FROM TERMINAL TO GROUND CONTINUITY WOULD KEEP CLIMBING, MEANING THE WINDS ARE NOT COMPLETELY BROKE BUT IT IS DEFINITELY ON THE WAY OUT. OTHER ISSUE COULD BE A RESTRICTION IN REFRIGERATION CIRCUT. COST OF REPAIR OVER REPLACEMENT, REPLACEMENT IS HIGHLY RECOMMEND