No heat Utica Gas Boiler. Found pilot not lighting, due to it being wet from water leak at expansion tank. Replaced expansion bladder tank, as well as air vent, and relief valve. Dried pilot assembly and relit pilot, after refilling and purging boiler. Tested for draft and carbon monoxide in flue to chimney.

No heat Utica Gas Boiler. Found pilot not lighting, due to it being wet from water leak at expansion tank. Replaced expansion bladder tank, as well as air vent, and relief valve.  Dried pilot assembly and relit pilot, after refilling and purging boiler. Tested for draft and carbon monoxide in flue to chimney.