Performed ac diagnostic, game room unit. Ac is the closest to the gate. Found thermostat off, turned system on airflow running. Went outside compressor and fan not running. Opened system up and found failed dual capacitor. Changed dual capacitor 35-5. Tested system. System cooling at this time.