3129 Swetzer Rd. # G
Loomis, CA 95650
916-577-5020

Job Locations
for north highlands, ca


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat


Map of North Highlands CA
Brandon B.

Brandon B.


Job Checkin

Performed annual heating maintenance north highlands. 21 yr gas package unit roof. System operational at this time. Washed eMaze filter. Tested parts. Blower capacitor 10@9.9. Spark ignitor ok. Cleaned burners and flame sensor. Inducer starting to loosin up. See video. Inducer .5 amps max .62. Wiring looks good. No loose connections. Control board ok no burn marks at this time. Inspected the heat exchanger found insulation laying on top of it see pictures, removed bad section. Indoor coil doesn’t appear to have dye leak at this time. Ran system Left quotes for tstat