Job Checkin

Found capacitor and contactor to be bad. Replaced both and the condenser still will not run. Had 24V to Contactor and it still will not run. Sending lead tech out in the morning. Double checked for insulation from yesterday found common and run wire for compressor connected backwards that would cause a compressor malfunction if unit was to run fixed wiring try testing system unit has different situation than yesterday indoor blower now not even coming on previous day blower would come on have no low-voltage to the outdoor unit. Inspected system found zone control board with cover panel off and zone control fan cycler disconnected. Further inspection found no 24 V power at zone control board. checked furnace have no 24 V power coming from control board. checked transformer have 24 V power coming from transformer. visual inspection of control board found control board with shorted out burned up connections for common side of 24 V connection. Replaced control board done at no charge to