DCM11 complete; AC; (2) F20201, (2) F18201 and (8) F16201 replaced. Systems 1,2,6,7! 8-10 are functioning as designed. Need to add 2 additional unit to future maintenance plan System #3 : system suffered an electrical burnout. Need to replace compressor wiring harness, wires ends burnt off. This fault was initially reported in May of 23, following is from Brad’s invoice “#3: Compressor leads extremely damaged / burned. Intermittent continuity between winding. Probably due to the terminals sustaining damage when compressor leads malfunctioned. Resistance through winding is accurate when electrical contact is made but again is intermittent. Recommend replacement of leads and capacitor ( 30/5 ) to determine if compressor is still mechanically/electrically intact” Tested windings, identified same intermittent continuity between windings, however when meter leads are pushed into the compressor terminals, ohm readings are in accordance with manufacturer specifications. System #4 : Extrem