Installed RSH-50 VRM line voltage monitor and surge protector. Added electrical whip between disconnect and monitor. Set monitor to over voltage lockout 255, under voltage lockout 225, lockout at .1 seconds out of range and to 4mins of constant proper voltage to turn back on. Tested system and monitor both are operating as designed. Photos attached.