Today I arrive to service call and noticed blower wheel was extremely dirty also evaporator coil needs cleaned. Disconnect box is exposed and have charred inside and along with no fuse. I check pressures and subcool is low and the compressor starving for refrigerant. It needs to be recharged maybe a couple of pounds. Suction line also doesn’t have armor flex installation it’s exposed. I explained to Club member this needs to be done in order to get unit back to operating properly. Club member wanted to start with these options first 1) electronic leak detection and Add Refrigerant 2) evaporator and Blower Wheel cleaning