The unit was cooling when I arrived,the thermostat has an alarm, A111_exv temp thermistor failure, I went to air handler and found condensation pump power source breaker off, turned on and condensation pump is operating,also found ptrap clogged, cleared, the inside of the air handler was full of water, the code went away, I told customer that if it continues we will need to replace temp thermistor.